EM24-2 Wet-Location Incandescent Emergency Unit

PRODUCT SPECIFICATIONS

 

ILLUMINATION

Sealed and gasketed weather proof lamp heads with tempered glass lenses. 

7.2W incandescent wedge base lamps. 

ELECTRICAL

Dual 120/277 voltage. 

Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. 

LVD (low voltage disconnect) prevents battery from deep discharge. 

6V maintenance-free, rechargeable Sealed lead acid battery. 

Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. 

Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. 

MOUNTING

External mounting brackets for simplified wall mounting provided. 

HOUSING

Corrosion-resistant 5VA flame retardant, UV-stabilized polycarbonate in gray finish. 

Sealed and gasketed housing with hinged cover. 

Sealed test switch. 

Integral breather vent. 

OPTIONS

HTR: Optional internal heater for cold temperature applications. 

USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. 

WARRANTY/LISTING

Five year warranty on all electronics and housing. Batteries are pro-rated warranted for two years. 

Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. 

UL listed for wet locations. (5°C – 40°C)